12.7/22kV Single Core
12.7/22kV Single Core
12.7/22kV XLPE Single Core Stranded Conductors up to 10kA fault level
Read moreDescription
Description
Standards
-
ProductAS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductor
- Semi-conductive conductor screen
- XLPE insulation
- Semi-conductive insulation screen
- Copper wire screen
- PVC sheath
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
280.0 kg/100m
Conductor cross-section
400 mm²
Conductor diameter
23.0 mm
Diameter over insulation
35.4 mm
Diameter over screen
39.9 mm
Nominal Duct Diameter Trefoil Single Way
65 mm
Nominal Duct Diameter in Single Way
150 mm
Nominal insulation thickness
5.5 mm
Nominal overall diameter
45.2 mm
Number of screen wires (nb x mm Ø)
48 x 1.35 mm Ø
Screen section
68.71 mm²
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. at 90 °C - flat formation
0.101 Ohm/km
A.C. Conductor resist. at 90 °C - trefoil formation
0.102 Ohm/km
Capacitance (All Main Cores - Screen)
0.363 µF / km
Charging current per phase
1.447 A/km
Dielectric loss per phase
73.5 W/km
Inductive reactance at 50Hz - flat touching
0.123 Ohm/km
Inductive reactance at 50Hz - trefoil
0.108 Ohm/km
Inductive reactance at 50Hz and 90°C flat spaced
0.169 Ohm/km
Insulation resistance at 20°C
6700 MOhm.km
Max. DC resistance of the conductor at 20°C
0.078 Ohm/km
Maximum electric stress
2.8 kV/mm
Permissible short circuit current conductor 1s
37.8 kA
Permissible short circuit current screen 1s
10.19 kA
Rated Voltage Uo/U (Um)
-
Resistance of the screen
0.26 Ohm/km
Zero sequence reactance at 50HZ
0.049 Ohm/km
Zero sequence resistance at 20°C
0.348 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
20 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
810 mm
Minimum Bend Radius - Installed
540 mm