1 x 1000 mm2 AL 12.7/22 kV XLPE/SCRN/PVC
1 x 1000 mm2 AL 12.7/22 kV XLPE/SCRN/PVC
12.7/22kV XLPE Single Core Stranded Conductors up to 10kA fault level
Read moreDescription
Description
Standards
-
ProductAS/NZS 1429.1; IEC 60228; IEC 60502-2
Construction
- Stranded compacted conductor
- Semi-conductive conductor screen
- XLPE insulation
- Semi-conductive insulation screen
- Copper wire screen
- PVC sheath
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor material
Aluminum
Insulation
XLPE
Outer sheath
PVC
Screen
Copper wire
Type of conductor
Stranded compacted
Dimensional characteristics
Dimensional characteristics
Approximate weight
540.0 kg/100m
Conductor cross-section
1000 mm²
Conductor diameter
40.2 mm
Diameter over insulation
54.3 mm
Diameter over screen
58.8 mm
Nominal Duct Diameter Trefoil Single Way
100 mm
Nominal Duct Diameter in Single Way
200 mm
Nominal insulation thickness
5.5 mm
Nominal overall diameter
65.1 mm
Number of screen wires (nb x mm Ø)
48 x 1.35 mm Ø
Screen section
68.71 mm²
Electrical characteristics
Electrical characteristics
A.C. Conductor resist. at 90 °C - flat formation
0.039 Ohm/km
A.C. Conductor resist. at 90 °C - trefoil formation
0.039 Ohm/km
Capacitance (All Main Cores - Screen)
0.597 µF / km
Charging current per phase
2.38 A/km
Dielectric loss per phase
121 W/km
Inductive reactance at 50Hz - flat touching
0.11 Ohm/km
Inductive reactance at 50Hz - trefoil
0.095 Ohm/km
Inductive reactance at 50Hz and 90°C flat spaced
0.155 Ohm/km
Insulation resistance at 20°C
4000 MOhm.km
Max. DC resistance of the conductor at 20°C
0.03 Ohm/km
Maximum electric stress
2.5 kV/mm
Permissible short circuit current conductor 1s
94.6 kA
Permissible short circuit current screen 1s
10.19 kA
Rated Voltage Uo/U (Um)
-
Resistance of the screen
0.26 Ohm/km
Zero sequence reactance at 50HZ
0.039 Ohm/km
Zero sequence resistance at 20°C
0.3 Ohm/km
Mechanical characteristics
Mechanical characteristics
Maximum Pulling Tension
50 kN
Usage characteristics
Usage characteristics
Minimum Bend Radius - During Installation (under Tension)
1170 mm
Minimum Bend Radius - Installed
780 mm