Single Core CU 8.7/10kV cable
Single Core CU 8.7/10kV cable
MV 8.7/10kV Cu Conductor XLPE Insulation Copper wire screen LSOH outer sheath Unarmored Power Cable
Read moreCU/XLPE/CWS/LSOH IEC60502 Cat C Copper-8.7/10kV-1X300
Nexans ref. 2031286409135
- Packaging: Cut to length (m)
- Conductor diameter: 20.5 mm
- Number of screen wires (nb x mm Ø): 44 x 0.85 mm Ø
- Nominal outer sheath thickness: 2.2 mm
- Outer Diameter: 39.4 mm
- Approximate weight: 376.6 kg/100m
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
- A.C. Conductor resist. at 90 °C - trefoil formation: 0.0779 Ohm/km
CU/XLPE/CWS/LSOH IEC60502 Cat C Copper-8.7/10kV-1X400
Nexans ref. 2031286409136
- Packaging: Cut to length (m)
- Conductor diameter: 23.2 mm
- Number of screen wires (nb x mm Ø): 44 x 0.85 mm Ø
- Nominal outer sheath thickness: 2.3 mm
- Outer Diameter: 42.3 mm
- Approximate weight: 470.7 kg/100m
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- A.C. Conductor resist. at 90 °C - trefoil formation: 0.0616 Ohm/km
CU/XLPE/CWS/LSOH IEC60502 Cat C Copper-8.7/10kV-1X70
Nexans ref. 2031286409129
- Packaging: Cut to length (m)
- Conductor diameter: 9.7 mm
- Number of screen wires (nb x mm Ø): 29 x 0.85 mm Ø
- Nominal outer sheath thickness: 1.8 mm
- Outer Diameter: 27.6 mm
- Approximate weight: 127.9 kg/100m
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- A.C. Conductor resist. at 90 °C - trefoil formation: 0.342 Ohm/km
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-2
-
TestIEC 60332-3-24 Cat.C; IEC 60754-1; IEC 60754-2; IEC 61034
Application
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas.
Construction
Conductor :Stranded compacted plain annealed copper in accordance to IEC 60228 Class 2
Conductor screen :Extruded semi-conducting compound comply with IEC 60502-2
Insulation:Extruded XLPE compound comply with IEC 60502-2.
Insulation screen :Extruded semi-conducting compound comply with IEC 60502-2
Metallic screen(CWS):1 layer copper wire applied helically over insulation screen with a layer of suitable tape.
Outer sheath:Extruded LSOH ST8 compound complied with IEC 60502-2, Color: Black
Operation condition
Rated voltage, U0/U(Um), kV: 8.7/10 (12)
Service temperature, static, ℃:-15~60
Max. conductor temperature in service, ℃:90
Min. bending radius, D overall diameter of cable:23D
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Resources
Resources
Selling & delivery Information
Marking on the outer surface of the sheath, along one line, for example as below:
NEXANS ELECTRIC CABLE CU/XLPE/CWS/LSOH 8.7/10kV 1C×400SQMM TO IEC 60502-2/IEC 60332-3-24