Single Core CU 8.7/10kV cable

Products

CU/XLPE/CWS/LSOH IEC60502 Cat C Recycled_Copper-8.7/10kV-1X300

Nexans ref. 2031286409135

  • Packaging: Cut to length (m)
  • Conductor diameter: 20.5 mm
  • Metallic cross-section: 25 mm²
  • Nominal outer sheath thickness: 2.2 mm
  • Nominal overall diameter: 36.8 mm
  • Approximate weight: 3528 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km

 

CU/XLPE/CWS/LSOH IEC60502 Cat C Recycled_Copper-8.7/10kV-1X400

Nexans ref. 2031286409136

  • Packaging: Cut to length (m)
  • Conductor diameter: 23.2 mm
  • Metallic cross-section: 35 mm²
  • Nominal outer sheath thickness: 2.3 mm
  • Nominal overall diameter: 39.9 mm
  • Approximate weight: 4374 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km

 

CU/XLPE/CWS/LSOH IEC60502 Cat C Recycled_Copper-8.7/10kV-1X70

Nexans ref. 2031286409129

  • Packaging: Cut to length (m)
  • Conductor diameter: 9.7 mm
  • Metallic cross-section: 16 mm²
  • Nominal outer sheath thickness: 1.8 mm
  • Nominal overall diameter: 25.0 mm
  • Approximate weight: 1126 kg/km
  • Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km

 

Description

Description

Standards

  • Product
    IEC 60228; IEC 60502-2
  • Test
    IEC 60332-3-24; IEC 60754; IEC 61034

Application

To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas.

Construction

Conductor: Stranded compacted plain annealed copper in accordance to IEC 60228 Class 2

Conductor screen: Extruded semi-conducting compound comply with IEC 60502-2

Insulation: Extruded XLPE compound comply with IEC 60502-2.

Insulation screen: Extruded semi-conducting compound comply with IEC 60502-2.

Metallic screen(CWS): 1 layer of plain annealed copper wire applied helically over insulation screen core.

Outer sheath: Extruded LSOH ST8 compound complied with IEC 60502-2, Color: Black

Operation condition

Rated voltage, U0/U(Um), kV: 8.7/10 (12)

Service temperature, static, ℃:-15~60

Min. installation temperature, ℃:0

Max. conductor temperature in service, ℃:90

Max. permissible short-circuit temperature,5sec, ℃:250

Min. bending radius, D overall diameter of cable:23D

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Type of conductor
Stranded compacted
Conductor material
Copper
Material of the inner semi-conductor
Extruded semiconducting compound
Insulation
XLPE
Material of the external semi-conductor
Extruded semiconducting compound - easy strippable
Screen
Copper wire
Outer sheath
LS0H polyolefin

Dimensional characteristics

Dimensional characteristics

Nominal insulation thickness
4.5 mm

Electrical characteristics

Electrical characteristics

Test voltage
30 kV
Voltage for partial discharge test
15.1 kV

Fire safety characteristics

Fire safety characteristics

Flame retardant
IEC 60322-1-2; IEC 60332-3-24
Halogen free
IEC 60754
Smoke density
IEC 61034

Resources

Resources

Selling & delivery Information

Marking on the outer surface of the sheath, along one line, for example as below:

NEXANS  ELECTRIC CABLE CU/XLPE/CWS/LSOH 8.7/10kV 1C×400SQMM TO IEC 60502-2

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close