Single Core CU 8.7/10kV cable
Single Core CU 8.7/10kV cable
MV10 CU XLPE CWS LSOH Recycled Copper 1C 70-400mm2
Read moreCU/XLPE/CWS/LSOH IEC60502 Cat C Recycled_Copper-8.7/10kV-1X300
Nexans ref. 2031286409135
- Packaging: Cut to length (m)
- Conductor diameter: 20.5 mm
- Metallic cross-section: 25 mm²
- Nominal outer sheath thickness: 2.2 mm
- Nominal overall diameter: 36.8 mm
- Approximate weight: 3528 kg/km
- Max. DC resistance of the conductor at 20°C: 0.0601 Ohm/km
CU/XLPE/CWS/LSOH IEC60502 Cat C Recycled_Copper-8.7/10kV-1X400
Nexans ref. 2031286409136
- Packaging: Cut to length (m)
- Conductor diameter: 23.2 mm
- Metallic cross-section: 35 mm²
- Nominal outer sheath thickness: 2.3 mm
- Nominal overall diameter: 39.9 mm
- Approximate weight: 4374 kg/km
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
CU/XLPE/CWS/LSOH IEC60502 Cat C Recycled_Copper-8.7/10kV-1X70
Nexans ref. 2031286409129
- Packaging: Cut to length (m)
- Conductor diameter: 9.7 mm
- Metallic cross-section: 16 mm²
- Nominal outer sheath thickness: 1.8 mm
- Nominal overall diameter: 25.0 mm
- Approximate weight: 1126 kg/km
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
Description
Description
Standards
-
ProductIEC 60228; IEC 60502-2
-
TestIEC 60332-3-24; IEC 60754; IEC 61034
Application
To be used for power distribution in medium voltage, as transformer feeders in substations. In power plants, industrial and operation installations, in residential areas.
Construction
Conductor: Stranded compacted plain annealed copper in accordance to IEC 60228 Class 2
Conductor screen: Extruded semi-conducting compound comply with IEC 60502-2
Insulation: Extruded XLPE compound comply with IEC 60502-2.
Insulation screen: Extruded semi-conducting compound comply with IEC 60502-2.
Metallic screen(CWS): 1 layer of plain annealed copper wire applied helically over insulation screen core.
Outer sheath: Extruded LSOH ST8 compound complied with IEC 60502-2, Color: Black
Operation condition
Rated voltage, U0/U(Um), kV: 8.7/10 (12)
Service temperature, static, ℃:-15~60
Min. installation temperature, ℃:0
Max. conductor temperature in service, ℃:90
Max. permissible short-circuit temperature,5sec, ℃:250
Min. bending radius, D overall diameter of cable:23D
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Fire safety characteristics
Fire safety characteristics
Resources
Resources
Selling & delivery Information
Marking on the outer surface of the sheath, along one line, for example as below:
NEXANS ELECTRIC CABLE CU/XLPE/CWS/LSOH 8.7/10kV 1C×400SQMM TO IEC 60502-2
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania