CU/XLPE/IS/OS/LSOH/SWA/LSOH-300/500-14Pr1

Description

Description

Standards

  • Product
    EN 50288-7
  • Test
    IEC 60332-3-22 Cat.A; IEC 60754-1; IEC 60754-2; IEC 61034

Application

These cables are used to transmit analogue or digital signals in measurement and process control system. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant…).

Construction

Conductor

Solid, stranded or flexible plain or metal coated copper in accordance with Class 1, 2 or 5 of EN 60228

Insulation

Extruded crosslinked polyethylene (XLPE) compound complied with EN 50290-2-29

Identification:

Pair(s): black and white insulation 
Triple(s): black, white and red insulation 

*for multi-pairs or triples, Each core identified through marking by inscription of a number on the core’s 
insulation and cores in a pair or triple marked with the same number

Pair(s) or triple(s)

Two or three insulated conductors shall be twisted together to form a pair or triple with non-hygroscopic binder 

Individual screen(for multi-pair or triads only)

A laminated aluminum backed polyester tape helically applied with 20% overlap to100% coverage and the metallic side 

down in electrical contact with a drain wire through the cable length.

A layer of non-hygroscopic tape helically applied around each screen to remain cable components isolated both from each 

other and the collective screen.

Cable make-up

The cable elements shall be assembled together in concentric layers, and the lay direction of out layer is right

Non-hygroscopic fillers may be used to maintain a substantial circular formation

Collective screen(Overall Screen)

A laminated aluminum backed polyester tape helically applied with 20% overlap to100% coverage with the metallic side 

down in electrical contact with a drain wire through the cable length.

Inner sheath

Extruded Low smoke halogen free polyolefin complied with EN 50290-2-27 ,flame retardant.

Color: Black

Metal amour

A layer of galvanized steel wire helically wrapped around the assembly cores with suitable binding tape.

Over sheath

Extruded Low smoke halogen free polyolefin complied with EN 50290-2-22,flame retardant.

Color: Black For non-intrinsically safe cable and Blue for intrinsically safe

Features

UV resistance ,UL 1581 Sect.1200 Upon request
Oil resistance 70℃ 4 h Upon request
Anti termite and rodent Upon request

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor flexibility
Class 2
Conductor shape
Circular stranded (RM)
Insulation
Cross-linked compound
Material of filler / inner sheath
Filler if necessary
Armour type
Galvanised round steel wires
Drain wire
Stranded tinned copper
Individual screen
Aluminium / Polyester tape
Outer sheath
Low smoke, zero halogen thermoplastic compound
Overall screen
Tinned copper drain wire + aluminium/polyester tape
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
1 mm²
Approximate weight
1378 kg/km
Nominal conductor diameter
1.29 mm
Nominal insulation thickness
0.44 mm
Nominal outer diameter
30.3 mm
Nominal outer sheath thickness
1.7 mm
Number of cores
14

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
300/500 V
Test voltage
2 kV

Usage characteristics

Usage characteristics

Bending factor when laying
15 (xD)
Max. conductor temperature in service
90 °C
Maximum operating temperature
90 °C
Minimum Bend Radius - Installed
12 mm
Minimum installation temperature
-10 °C
Oil resistance
No
Operating temperature, range
-15 ... 90 °C
Resistant to termites
No
Rodent resistant
No
Short-circuit max. conductor temperature
250 °C
U.V resistance
if required

Fire safety characteristics

Fire safety characteristics

Fire retardant
EN IEC 60332-3-22 (cat A)
Gases corrosivity
IEC 60754-2
Gases toxicity
IEC 61034, IEC 60754-2
Halogen free
IEC 60754-2

Resources

Resources

Selling & delivery Information

Cable marking

Inkjet print
NEXANS CU/XLPE/OS/LSOH/SWA/LSOH 300/500V < N>Pair < S>SQMM EN 50288-7 IEC 60332 3 24 Cat C YYYY ****M 
NEXANS CU/XLPE/IS/OS/LSOH/SWA/LSOH 300/500V < N>Triads< S>SQMM EN 50288-7 IEC 60332 3 24 Cat C YYYY ****M 
N Number of pairs/triads
S Nom. cross sectional area
YYYY The year of manufacture
M meter marking by inkjet with increased sequence with numbering

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close